 AC-DC DIN Rail 50-200 Watts DRF Series
*
THE XPERTS IN POWER
Input 187-528 VAC 1O * Adjustable Output * High Peak Current Capability * Overvoltage Protection * Overcurrent Protection * International Safety Approvals
Specification
Input
Input Voltage Input Frequency Input Current Inrush Current Power Factor Leakage Current * * * * * * 187-528 VAC single phase (264-746 DC) 47-63 Hz 1.1 A max @ 240 VAC 25/50 A typical @ 240/480 VAC cold start +25 C 0.98/0.93 typical at 240/480 VAC for DRF200 0.75 mA max (1.5 mA DRF200)
General
Efficiency Isolation * * 82% typical at 240 VAC 3000 VAC Input to Output 2000 VAC Input to Ground 500 VAC Output to Ground 120 kHz PWM, 50 kHz PFC (DRF200)
Switching Frequency *
Environmental
Operating Temperature Storage Temperature Humidity Shock Vibration * * * * * -10 C to +70 C (+60 C DRF200) Contact Technical Sales for derating -20 C to +75 C 20-90% non condensing 20 G, 11 ms once on the X axis 2 G 10-55 Hz 3 axis
Output
Output Voltage Output Voltage Adjustment Minimum Load Start Up Time Hold Up Time Drift Line Regulation Load Regulation Ripple & Noise Overvoltage Protection Overcurrent Protection Temperature Coefficient Thermal Protection * * * * * * * * * * 24 VDC nominal 10% No minimum load required 800 ms max with 240 VAC 10 ms (100 ms DRF200) typical at 240 VAC & 100% load 100 mV max 96 mV max 150 mV 0-100% load, 480 mV max 0-peak load 680 mV pk-pk max 20 MHz bandwidth & 100% load 115-150% of nominal rating, recycle input to reset 240 VAC & 100% load >105% of peak current, auto recovery 0.04%/C Recycle input to reset
EMC & Safety
Emissions ESD Susceptability Radiated Susceptibility EFT/Burst Surge Safety Approvals * * * * * * EN55022 Level A conducted EN55022 Level A radiated EN61000-4-2 Level 2 (Level 4 DRF200) EN61000-4-3 Level 3 EN61000-4-4 Level 4 EN61000-4-5 Level 3 UL1950, cUL, EN60950, EN50178
* * *
*
*
www.xpplc.com
sales@xpplc.com
OUTPUT VOLTAGE & CURRENT RATINGS
Output Voltage 21.6 - 26.4 V 21.6 - 26.4 V 21.6 - 26.4 V Notes
1. Peak current for 150 ms in every 30 second period. Only available with an input voltage of 240 to 528 VAC.
DRF
Peak(1) 6.7 A 10.0 A 42.0 A Model Number DRF50US24-N1 DRF75US24-N1 DRF200PS24-N1
Output Current Nominal 2.1 A 3.1 A 8.4 A
*
Mechanical Details
DRF50 Model Weight: <630g
DRF200 Model Weight: <1700g
DRF75 Model Weight:<750g
Peak Loading Curves
NOTE: ( ) for DRF200 models t 150 ms, 30 s T (t 50 ms, 30 s T DRF200)
www.xpplc.com
sales@xpplc.com
Rev 3.0


▲Up To Search▲   

 
Price & Availability of DRF50US24-N1

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X