![]() |
|
If you can't view the Datasheet, Please click here to try to view without PDF Reader . |
|
Datasheet File OCR Text: |
Emergency Stop Relay/Safety Gate Monitor Type BN 5983 safemaster Features * Category 3 * Contacts .53 - 3 N/O, 1 N/C, 1 N/O 200ms delayed release on reset .53/101 - 3 N/O, 1 N/C, 1 N/O 1 sec delayed release on reset .54 - 3 N/O, 1 N/C, 1 N/O * Removable terminal strips for fast replacement www..com Models BN 5983.53, BN 5983.53/101, BN 5983.54 * Front mounted auxiliary supply fuse * AC or 24V DC auxiliary supply options * Single channel or dual channel operation * Manual or automatic reset TUV Rheinland CANADA USA SWEDEN Technical Committee of Electrical Engineering Typical Schematic Diagram Description BN 5953.53, BN 5983.53/101 L OFF A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 K3 K2 K1 EMERG. STOP S12 S22 X3 X4 Emergency Stop Relay Type BN 5983 complies fully with the requirements of the Standard Specifications referred to on page 3 of this Publication. The unit is housed in a compact 100mm wide case suitable for DIN rail mounting and is available in a wide range of auxiliary voltages. BN 5983.53/101 has a one second delay on reset, a useful feature when using this relay as a combined Emergency Stop/gate monitor. These relays are extensively used and specified by the UK/ European automotive industry. Circuit Connections A2 14 24 34 54 42 (-) ON/RESET N Diag 1 Relay BN 5983 operates on the principle described on page 6 of this catalogue. The OFF and the EMERGENCY STOP buttons are connected in series between terminals S11 and S12/S22. The On/Reset button is connected between terminals S12 and X4. The auxiliary supply is connected to terminals A1(+) and A2(-). The circuits to be tripped may be connected to terminals 13-14, 23-24 and 33-34. Remote signalling circuitry, if applicable, is connected to terminals 41-42, 53-54. For additional security an insulation monitoring relay may be connected to monitor terminal PE(-) to ground. (Relay details on request). This relay is suitable for category 3 applications. BN 5983.53 with External Contactors This diagram shows how external contactors with positive guided contacts C1 and C2 may be used to reinforce the switching capacity of BN 5983 with continued redundancy. Special Note L OFF A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 C1.2 K3 K2 C2.2 K1 EMERG. STOP S12 S22 X3 C1.1 C2.1 X4 It is recommended that redundancy is carried through to the EMERGENCY STOP button by using a dual contact button as shown. If a single contact button is used then terminals S12 and S22 should be bridged (category 2 applications only). Indication A2 14 24 34 54 42 (-) The relay is equipped with two green LEDs. When illuminated they indicate the healthy condition of circuits K2 and K3. L C1 C2 ON/RESET N Diag 2 8 Emergency Stop Relay/Safety Gate Monitor Type BN 5983 safemaster Additional Information Dimensions If additional switching contacts are required then Relay BN 5983 may be used with extension module Type BN 3081 (diag. 7). Should a delayed release contact be required then BN 5983 may be used with time delay modules BG 7925 / IL 7824 / IN 7824 / BA 7924 (see below). Model BN 5983 and /101 may be used with protective guards/screens, but for this application reference is made to the dedicated gate monitors Model BD 5985 - BN 5986 shown on page 53 - 54. Gold plated contacts are available as an optional extra should very low switching currents be required. www..com If single channel high voltage AC pushbutton control is required (Risk Level 2) terminals S11, S12 - S22 should be linked and the Emergency Stop pushbuttons connected in series with terminal A1. (see also BN 5930/204). Schematic Diagram BN 5983.53 or /101 used as a safety gate monitor with auto reset Version BN 5983.54 L L OFF A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 K3 K2 K1 EMERG. STOP S12 S22 X3 X4 K3 GATE CLOSED S2 K2 K1 S1 S12 S22 X3 X4 A2 14 24 34 54 42 (-) A2 14 24 34 54 42 (-) N N ON/RESET Diag 3 Diag 5 BN 5983.53 used as a safety gate monitor with infinite time delay between S12 and S22 closing. BN 5983.53 with additional delayed release safety timer IL 7824, IN 7824, BA 7924 L 24Vdc +VE OFF A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 K3 K2 K1 EMERG. STOP S12 S22 X3 X4 A1 27 15 K3 DELAYED RELEASE TIMED CONTACT GATE CLOSED S2 A2 28 16 K2 K1 S1 S12 S22 X3 X4 A2 14 24 34 54 42 (-) A2 14 24 34 54 42 (-) ON/RESET N - VE Diag 4 Diag 6 9 Emergency Stop Relay/Safety Gate Monitor Type BN 5983 safemaster BN 5983 with BN 3081 Extension modules +24V OFF A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 A1 A3 13 23 33 43 53 63 73 81 A1 A3 13 23 33 43 53 63 73 81 K3 K2 K1 EMERG. STOP K1 K2 K1 K2 www..com A2 S12 S22 X3 X4 14 24 34 54 42 (-) A2 A4 14 24 34 44 54 64 74 82 A2 A4 14 24 34 44 54 64 74 82 0V ON/RESET BN 5983.53 BN 3081 BN 3081 Diag 7 Specifications BN 5983.53 with link monitoring of the ON/Reset button for light barrier applications Nominal Voltage (Vn) Burden Voltage Tolerance Frequency Control Voltage Min. return voltage Contacts Max Switching Capacity Continuous Current Rating Contact Life Mechanical Contact Life Electrical Derated Capacity (for Heavy Inductive Loads) Min Switching Voltage & Current Max Switching Voltage Max Switching Power Max Switching Frequency Max Loop Resistance Reaction times Operating Temperature Protection Class Test Voltage Shock Loading Enclosure Material Terminations 24,48,110,127,230V ac or 24V dc (To be Specified) <5VA ac/3W 24V dc 0*8-1.1 Vn ac. 0*8-1*2 Vn dc 50 to 60Hz 5% 24V dc (S11) 18*5V dc (S12/S22) .53 3N/O, 1N/C plus 1 N/O 200ms delayed release, on reset .53/101 version 1 sec delayed release on reset .54 3N/O, 1 N/C, 1N/O 10A ac (cos o 1 - 0*7) 10A dc see page 84 see page 84 30 x 106 operations see page 84 AC15, 6A, 250V ac DC13, 6A, 24V dc 10V, 15mA ac/dc 415V ac 250V dc 2500VA (AC1)/240W dc 6000 operations/hour 110 S11/S12-S22 Dual Channel Operation Reset 200ms/1sec ESTOP<20ms -15C ... +55C at 90% RH Case IP40 Terminals IP20 2*5KV 1 minute Amplitude 0.35mm Frequency 10-55Hz (5g @ 50Hz) Thermoplastic Vo Rating UL94 2 x 2*5mm2 solid 2 x 1*5mm2 stranded L OFF A1 PE (+) (-) S11 S34 13 23 33 53 41 X5 K3 K2 EMERG. STOP K1 LIGHT BARRIER S12 S22 X3 X4 A2 14 24 34 54 42 (-) ON/RESET N Diag 8 Fuse Rating Front mounted fuse rating 230V ac 110V ac 24V ac 24V dc - - - - T32mA/250V T50mA/250V m250mA/250V m1A/250V } 20 x 5mm Glass Information Required With Order * Model type * Auxiliary supply Example: Emergency Stop Relay Type BN 5983.53 Auxiliary Supply 230V 50Hz 10 |
Price & Availability of BN5983
![]() |
|
|
All Rights Reserved © IC-ON-LINE 2003 - 2022 |
[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy] |
Mirror Sites : [www.datasheet.hk]
[www.maxim4u.com] [www.ic-on-line.cn]
[www.ic-on-line.com] [www.ic-on-line.net]
[www.alldatasheet.com.cn]
[www.gdcy.com]
[www.gdcy.net] |