  enhance d communication module (pr ofibus) [pumcp] pumcp is a communication module, which connects module type temperature controller pum series with profibus system. compatible with profibus dp-v0, and designed for high-speed communication at the maximum speed of 12mbps. being able to up to 16 units (64 channel) of puma (control module), pumcp requires minimum wiring, less space, and saves labor for engineering. fe atures i. program-less connection to profibus 1. profibus dp-v0 compatible high-speed communication at max.12mbps 2. access to all parameters of control module (puma/ pumb) via profibus 3. high-speed data communication with connected control modules (puma/pumb) - quick data importing and setting data refection ii. user-friendly structure and functions 1. lateral connection : max.16 units (64 channels) + event input/output module 16 units = total 32 units simple wiring for power supply and communication 2. detachable structure: terminal block, main unit, and the base part easy wiring with detachable terminal blcok main units exchangeable without re-wiring sys tem specif ication 1. product type: multi-loop module type temperature controller 2. module type 1) analog module: total maximum 16 units a) control module (4 loop/unit) b) extended input/output module - analog input/output module (input/output 4 points/unit) - analog input module (input 4 points/unit) - analog output module (output 4 points/unit) 2) extended input/output (digital) module: maximum 16 units - event input/output module (input/output ; 8 points/unit) 3) enhanced communication module: 1 unit 3. connecting method: lateral connecting with connectors - for power supply and rs-485 communication, any one of connected modules is required to be connected. 4. no. of loop, input/output 1) control loop: max. 64 2) no.of input / output: di 128 points / do 128 points pum series multi-loop module type temperature controller pumcp data sheet EDS11-172A apr. 1, 2011 date enhanc e d communication modul e (pr ofibus) specif ication 1. general specifcation (1) power supply: 24v dc 10% (2) power consumption: max. 3.2 w (135 ma) [when 24v dc is applied] (3) insulation resistance: 20m w or more (500v dc) (4) withstand voltage: power supply ? loader communication 1000v ac 1 min. power supply ? sld/fg terminal, profi - bus communication 1000v ac 1 min. (5) applied standards: ul, c-ul, ce marking, rohs directive [pending for ul and c-ul] 2. profibus communication module 2.1 profibus communication (1) compliant version: profibus dp-v0 (cyclic com - munication) (2) station type: slave device (3) communication speed and distance speed 9.6,19.2, 93.75 kbps 187.5 kbps 500 kbps 1.5mbps 3m,6m, 12mbps distance 1200m or less 100m or less 400m or less 200m or less 100m or less (4) station number: settable station number 1 to 99 (5) communication data length (cyclic communication) remote input/output bits remote input/output words 64 bits 8 words 128 bits 16 words 256 bits 32 words 512 bits 64 words 864 bits 108 words (6) connecting cable: type a compatible cable for profibus (7) connecting method: m3 screw terminal block (8) termination resistace: external (220 w , 1/2w) or depends on the internal sw setting.
pumcp 2 2.2 display, confguration (1) display: status display led (2 colors 2 points + 1 point) (2) display contents: run/fault, control module connection status (tx/rx), profibus status (onl) (3) setting device and set contents setting device set contents front rotary sw 2 profibus station no. set - ting inside dip sw (3bits) 1 word setting of data ex - change 3. power outage (1) impact of power outage: outage of 2ms or less ; no impact (2) operation after power outage: start from the frst step (cold start) (3) memory backup: nonvolatile memory (eeprom) no. of update ; 100,000 4. self diagnosis diagnosis method: program error monitoring by watch dog timer 5. structure (1) installation method: din rail mounting or mounting with m3 screws inside a cabinet (2) dimensions: 30 (w) 100 (h) 85 (d) mm (excluding terminal cover and projected part) (3) weight: approx. 200 g (4) extrenal terminal - profibus communication: detachable terminal block (m3 screw 20 terminals) - power supply connection: terminal block on the base part (m3 screw 2 terminals) power is supplied via side connectors in case of lateral connecting. (max. 33 units) - loader communication port: 2.5 diameter mini-plug / jack [on the front of the module] (5) case material: polyphenylene oxide (fame retardant grade : ul94v-0 equiva - lent) (6) case color: case ; red terminal, base part ; black (7) protection - body: ip20 grade protection (ventilation slits on the top and the bot - tom of the body) - terminal: ip00 grade protection, terminal cover is available as an option 6. normal operating condition (1) ambient temperature*: -10 to 50c * ambient temperature is the tempera - ture underneath the controller inside the equpiment or the cabinet where the controller is installed. (2) ambient humidity: 90% rh or less (non condensing) (3) vibration: 10 to 70hz, 9.8m/s 2 (1g) or less 7. transporting, storage condition (packing con - dition) (1) storage temperature: -20 to 60c (2) ambient humidity: 90%rh or less (no condensing) (3) vibration: 10 to 70hz, 9.8m/s 2 (1g) or less (4) shock: 294m/s 2 (30g) or less 8. packing list temperature controller: 1unit instruction manual: 1 copy 9. loader software (1) distribution medium: free download from fuji electric sys - tems hp (http://www.fc-net.jp/eng/index. html) (2) recommended operating environment pc: dos/v (pc-at compatible) os: windows xp (operation confirmed in japanese / english) ram: 256m bytes or more free space on the hardware: 500m bytes or more display resolution: 1024 768 dots or over serial interface: rs-232c 1 port (without rs-232c, usb serial converter cable required) (3) connection with pum via loader interface on the front face of the module (special cable available from fuji is required) cod e symbols [enhanced communication module] [accessories] d e scr i p t i o n 4 5 10 c p a b < m o d u l e t y p e > e n h a n c e d c o m m u n i c a ti o n m o d u l e < c o m m u n i c a t i o n f u n c t i o n > profibus co m m u n i ca t i o n < o p e r a t i o n m a n u a l > j a p a n e s e e n g l i s h digit 4 5 6 7 8 9 1 0 1 2 3 p u m y y digit 10 d e scr i p t i o n 6 7 8 a a a l 0 0 0 0 2 3 4 1 d i n r a i l m o u n t i n g e n d p l a t e s i d e co n n e t i n g t e r m i n a l co ve r ( r i g h t & l e f t 1 se t ) f r o n t f a ce scr e w t e r m i n a l co ve r l o a d e r co n n e ct i n g ca b l e ( r s - 2 3 2 c ) %jhju 4 5 6 7 8 1 2 3 p u m z * digit p o w e r l o a d e r co m m u n i ca t i o n p o r t profibus co m m u n i ca t i o n f u n ct i o n a l i n su l a t i o n ( 1 0 0 0 v a c ) f u n ct i o n a l i n su l a t i o n ( 5 0 0 v a c ) [t able 1] i nsulation block diagram
3 outline dia gram (u nit : mm) please keep the distance of 30mm from this instrument to radiate. [50mm is recommended] front terminal cover (option) (10) 30 100 50 6.1 1.5 5 6 at mounting to the din rail (8) 85 din rail main unit (at attach/detach) (30) locking tab hole for screw mounting base part (main unit is detached) dimensions for screw mounting (30) 90.2 2-m3 (100) 88.50.2 (3) notice at the installation 30 or more 30 or more +0.2 +0.7 30 loader station no. 10 1 terminal screw m3 terminal block (at attach/detach) hole for screw mounting terminal screw m3
pumcp 4 terminal connection dia gram loader 11 12 22 21 13 14 15 16 17 18 19 20 23 24 25 26 27 28 29 30 1 2 3 4 5 base part power + - 2 1 dont connect 3 4 5 1 2 3 gnd rx tx loader interface plug (rs-232c) 2.5 3-pole miniature plug station no. 10 1 11 14 15 13 12 19 20 17 18 16 dont connect dc24v 24 25 22 21 23 29 30 27 26 28 fg sld 2m 2p5 rts a(?) b(+) dont connect
5 profibus communication module status contents readout/write data setting range factory-set value register no. setting error 0101h: st. no. confguration sw (st. no.) is invalid value 0102h: dip sw (no. of words to exchange data) is invalid value 0203h: st. no. stored in eeprom is invalid value 0204h: no. of words to exchange data that is stored in eeprom is invalid value 0205h: exchange pattern of output data is invalid value 0206h: exchange pattern of input data is invalid value 0207h: output area device size is invalid value 0208h: input area device size is invalid value 0209h: window communication pattern is invalid value 020ah: output area st. no. is invalid value 020bh: output area register no. is invalid value 020ch: input area st. no. is invalid value 020dh: input area register no. is invalid value 0211h: window communication (eeprom) is invalid value 30232
pumcp 6 profibus communication setting contents readout/write data setting range factory-set value register no. profibus communication st. no. 1 to 125 1 40001 profibus communication setting for output area 0 : 0 word 1 : 8 words 2 : 16 words 3 : 32 words 4 : 64 words 5 : 108 words 0 40003 profibus communication setting for input area 0 : 0 word 1 : 8 words 2 : 16 words 3 : 32 words 4 : 64 words 5 : 108 words 0 40004 output area device size 0 to 108 words 0 40104 input area device size 0 to 108 words 0 40105 window communication pattern 0: no window communication 1: 1-word data communication 2: 2-word data communication 3: 4-word data communication 4: 8-word data communication *the above is the max. no. of words 0 40106
7 memory allocation (output area) contents readout/write data setting range factory-set value register no. output area entry st. no. (1st word) 0: not used 1 to 16: control/analog module 17 to 32: event module note: other than the above are not settable 0 41001 output area entry register no. (1st word) 0,40000 to 49999 (note1) 0 41002 output area entry st. no. (2nd word) 0: not used 1 to 16: control/analog module 17 to 32: event module note: other than the above are not settable 0 41003 output area entry register no. (2nd word) 0, 40000 to 49999 (note1) 0 41004 output area entry st. no. (108th word) 0: not used 1 to 16: control/analog module 17 to 32: event module note: other than the above are not settable 0 41215 output area entry register no. (108th word) 0, 40000 to 49999 (note1) 0 41216 note1: only the addresses written in output/input area register no. (users manual: profibus communication module inp- tn5a0489-e) are settable. however, the parameters marked * in entry ban column are not settable. memory allocation (input area) contents readout/write data setting range factory-set value register no. input area entry st. no. (1st word) 0: not used 1 to 16: control/analog module 17 to 32: event module note: other than the above are not settable 0 43001 input area entry register no. (1st word) 0, 30000 to 49999 (note2) 0 43002 input area entry st. no. (2nd word) 0: not used 1 to 16: control/analog module 17 to 32: event module note: other than the above are not settable 0 43003 input area entry register no. (2nd word) 0, 30000 to 49999 (note2) 0 43004 input area entry st. no. (108th word) 0: not used 1 to 16: control/analog module 17 to 32: event module note: other than the above are not settable 0 43215 input area entry register no. (108th word) 0, 30000 to 49999 (note2) 0 43216 note2: only the addresses written in output/input area register no. (users manual: profibus communication module inp- tn5a0489-e) are settable. however, the parameters marked * in entry ban column are not settable.
pumcp printed in japan caution on safety *before using this product, be sure to read its instruction manual in advance. international sales div sales group gate city ohsaki, east t ower , 1 1-2, osaki 1-chome, shinagawa-ku, t okyo 141-0032, japan http://www .fujielectric.com phone: 81-3-5435-7280, 7281 fax: 81-3-5435-7425 http://www .fjielectric.com/products/instruments/ information in this catalog is subject to change without notice.


▲Up To Search▲   

 
Price & Availability of EDS11-172A

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X