(1/2) 003-01 / 20080817 / e9131_zag_m.fm ? all specifications are subject to change without notice. emc filters for ac power line for single-phase, mid-size box cased zag-m series features the zag-m series employ a highly efficient thermal design, which ensures high current handling capacity in a compact package with superior emc suppression characteristics. they are highly effective at preventing both the radiation and penetration of emc noise. the parts are, therefore, highly immune to externally generated noise and do not, themselves, serve as sources of radiated noise. this product provides superior attenuation for both differential mode and common mode noise components. withstand voltage is ac.1768v between the lines and ac.1500v between line and ground. these filters are highly reliable and provide stable attenuation performance even in harsh environments, where the filters may be subjected to humidity, vibration , and shock. it is a product conforming to rohs directive. safety standard applications computers, hard disk drives, electronic exchange devices, nc control devices, large copiers, etc. shapes and dimensions dimensions in mm case: metal, terminal: stud electrical characteristics conformity to rohs directive part no. standard and standard no. canada csa c22.2 no.8 ZAG2250-M lr76849c csa part no. abcdef?ghi j kl ZAG2250-M 87 175 65 237 68 195 m6 5.5 32 39.8 14.2 215 part no. ZAG2250-M rated voltage eac(v) 250 rated current(a) 50 test voltage eac(v)[between terminal and case] 1500 insulation resistance(m ? )[dc. 500v, 1min/between terminal and case] 100min. leakage current(ma)[250v 60hz] 1.2max. dc resistance(m ? ) 3.6max. operating temperature range(c)[including self-temperature rise] ?10 to +85 with derating over(c) 55 temperature rise(c) 35max. attenuation frequency range (mhz)[+5 to +35c] differential mode at 30db 0.5 to 30 common mode at 20db 0.5 to 30 weight(kg) 1.5 c k j h a ?g i ?h e b f d l ground terminal 1 2 4 3 conformity to rohs directive: this means that, in conformity with eu directive 2002/95/ec, lead, cadmium, mercury, hexavalent chromium, and specific bromine-based flame retardants, pbb and pbde, have not been used, except for exempted applications.
(2/2) 003-01 / 20080817 / e9131_zag_m.fm all specifications are subject to change without notice. typical electrical characteristics attenuation vs. frequency characteristics pulse attenuation characteristics ZAG2250-M ZAG2250-M circuit diagram 100 80 60 40 20 0 0.1 0.3 1 3 10 30 100 frequency ( mhz ) attenuation ( db ) common mode differential mode 300 250 200 150 100 0 input voltage ( v ) 0 500 1000 1500 2000 output voltage ( v ) 50 pulse width: 1 s differential mode common mode 1 2 4 3 r r: bleeder resistor case gnd ground terminal
|