page 1 of 3 ac/dc power modules tml 100c series, 85-100 watt the tml 100c series modules are very compact 85C100 watt power supplies in a fully encapsulated plastic case. active power factor correction and high effciency across full load range qualify these modules for installation in energy related prod - ucts. they feature screw terminals for easy installation. the tml 100c series is accompanied by an international safety approval package for worldwide markets. features very compact power modules with screw terminal connection active pfc, power factor >0.95 (230vac), >0.99 (115 vac) high effciency up to 93% typ. remote on/off input adjustable output voltage 5% led output indicator universal input 100-240 vac nominal low leakage current emi meets en 55022, class b protection class ll prepared order code output power max. output voltage output current max. effciency 115 vac / 230 vac tml 100-112c 85 12 vdc 7000 ma 89.5 % / 91.0 % tml 100-115c 85 15 vdc 5660 ma 90.0 % / 91.5 % tml 100-124c 100 24 vdc 4200 ma 92.5 % / 93.5 % tml 100-148c 100 48 vdc 2100 ma 93.0 % / 94.5 % models ul 60950-1 c b scheme series description datasheet tmlm 04 4 watt, pcb mount, single and dual output models tmlm 05 5 watt, pcb mount, single output models www.tracopower.com/products/tmlm.pdf tmlm 10 10 watt, pcb mount, single output models tmlm 20 20 watt, pcb mount, single output models (compact design) tml 20 20 watt, pcb & chassis mount, single, dual and triple output models www.tracopower.com/products/tml.pdf tml 40 40 watt, pcb & chassis mount, single, dual and triple output models full tml and tmlm series model range http://www.tracopower.com
page 2 of 3 all specifcations valid at nominal input voltage, full load and +25c after warm-up time unless otherwise stated. ac/dc power modules tml 100c series 85-100 watt input specifications input voltage ranges C nominal 100 C 240 vac (universal input) C ac full range 90 C 264 vac C dc input 120 C 370 vdc input frequency 47 C 63 hz input current at full load (115 vac / 230 vac nominal input) < 2.0 a / < 1.0 a max. leakage current 0.5 ma max. harmonic limits en 61000-3-2, class a C power factor >0.99 at 115 vac, >0.95 at 230 vac leakage current <250 a output specifications voltage set accuracy 2 % output voltage adjustment range 5% (see page 3) minimum load 3% of rated max current (operation at lower load condition is safe but a higher output ripple will be experianced) ripple and noise (20 mhz bandwidth) 12 vdc model: 120 mv max. 15 vdc model: 150 mv max. 24 vdc model: 200 mv max. 48 vdc model: 240 mv max. regulation C input variation 1% C load variation 1% current limitation 105% C 180% of rated output power. (automatic recovery) overvoltage protection by zehner diode. short circuit protection indefinite (hiccup, automatic recovery) hold-up time 10 ms min. (110vac) max. capacitive load 12 vdc model: 50000 f 15 vdc model: 40000 f 24 vdc model: 6000 f 48 vdc model: 1000 f general specifications temperature ranges C operating C25c to +70c C power derating above +50c 2.0 %/k C case max. +95c C storage (non operating) C25c to +85c temperature coefficient 0.03 %/c efficiency see model table remote on/off control on: open or connection to -vout off: external +5vdc humidity (non condensing) 95 % rel max. switching frequency (pulse width modulation pwm) 10 0 C133 k h z isolation voltage C input/output 3000 vac reliability /calculated mtbf (mil-hdbk-217f, at +25c, ground benign) >250000 h environmental compliance C reach www.tracopower.com/products/tml-reach.pdf C rohs rohs directive 2011/65/eu http://www.tracopower.com
page 3 of 3 ac/dc power modules tml 100c series 85-100 watt rev. february 07. 2014 general specifications electromagnetic compatibility (emc), emissions en 61000-3-2:2006+a1:2009+a2:2009 en 61000-3-3:2008 en 55022, class b electromagnetic compatibility (emc), immunity en 55024 : 2010 C electrostatic discharge esd (air/contact) en 61000-4-2 2 kv / 4 kv, criteria a C rf field susceptibility en 61000-4-3 3 v/m, criteria a C electrical fast transient / burst immunity input en 61000-4-4 1 kv, criteria a C surge immunity line C neutral en 61000-4-5, 1 kv, criteria a C surge immunity line C pe, neutral C pe en 61000-4-5 2 kv, criteria a C immunity to conducted rf disturbances en 61000-4-6 3 v, criteria a C power frequency magnetic field immunity en 61000-4-8 1 a/m, criteria a C mains voltage dips and interruptions en 61000-4-11 30 % 500 ms, criteria a 95 % 10 ms, criteria a 95 % 2500 ms, criteria c protection class class i and class ii prepared safety standards iec 60950-1 2nd ed +am1 en 60950 -1: 2006/a11:2009/a1:2010/a12:2011 ul 60950-1 2nd ed +am1 safety approvals C cb certificate for iec/en 60950-1 www.tracopower.com/products/tml100c-cb.pdf C ul/cul 60950-1 (online certification) www.ul.com file e188913 casing material plastic resin + fiberglass (ul 94v-0 rated ) output voltage 12 vd c 15 vd c 24 vdc 48 vdc +5% 85 95 90 85 nominal open open open open C5% 220 300 600 150 0 trim up: resistor from trim to -vout (conection 7-6) trim down: resistor from trim to +vout (conection 7-5) output voltage adjustment ( trim resistor [kohm]) weight : 440 g ( 11. 5 o z ) dimensions in[mm], () = inches tolerances = 0.5mm (0.02) outline dimensions connection con. output 1 ac in (l) 2 ac in (n) 3 fg 4 remote on/off 5 +vout 6 -vout 7 trim 6 6.0 128.0 140.0 (5.12) (5.6) (0.24) 50.0 (2.0) 62.0 (2.48) 6.0 (0.24) 4 x ?3.2 (4 x ?0.1.26) 1 2 3 5 4 7 top view 36.6 (1.46) 6.6 (0.26) bottom view 4 x ?2.5 (4 x ?0.10) 4 x ?3.0 (4 x ?0.12) 24.0 (0.96) 13.0 (0.52) led sp ec i?cati ons can be changed wi thout noti ce! make sure you are using the latest documentation, downloadable at www.tracopower. com www .tracopower. com
|