  mvad065.b01 page 1 of 7 power.murata.com features ? ? ite (2nd ed.) and medical (3rd ed.) mopp safety approved ? ? 55-65w compact high density ? ? 2" x 4" standard footprint ? ? high effciency up to 90% ? ? remote sense ? ? universal ac input ? ? low profle - 1u package ? ? convection-cooled operation up to 65w ? ? complies with 5000m altitude ? ? rohs compliant ? ? input power < 74w ? ? ul class i and ii approved ? ? less than 0.3w no load input power ? ? complies with erp/energy star requirement excluding 5v output ordering guide model number natural convection cooling main output (v1) mvad065-05 55w 5v mvad065-12 60w 12v MVAD065-18 18v mvad065-24 65w 24v mvad065-48 48v input characteristics parameter conditions min. typ. max. units input voltage operating range single phase 90 120/230 264 vac dc 120 300 vdc input frequency 47 50/60 63 hz turn-on input voltage input rising at full load 70 85 vac turn-off input voltage input falling at full load 70 85 input current 90vac input, full load 1.4 a inrush current 5v at 264vac, at 25c cold start 75 apk other 60 output characteristics model number main output voltage (v1) load current load capacitance line, load, cross regulation typical effciency @230vac full load mvad065-05 5v 0 to 11a 0 to 2200f 2% 84% mvad065-12 12v 0 to 5.0a 0 to 1000f 2% 88% MVAD065-18 18v 0 to 3.34a 0 to 680f 2% 86% mvad065-24 24v 0 to 2.71a 0 to 560f 2% 89% mvad065-48 48v 0 to 1.36a 0 to 330f 2% 90% main output characteristics parameter conditions min. max. units 5v other transient response 50% load step, 1a/sec slew rate 5 % settling time to 1% of nominal 500 200 sec turn on delay after application of input power 1 sec output voltage rise monotonic, 0 to 100% load 50 msec setpoint accuracy 120vac, 40w, 25c 1 0.5 % output holdup 115vac, 100% load 10 msec temperature coeffcient 0.02 %/c ripple voltage & noise 1 2 1 % remote sense 3 compensates for up to 400mv of lead drop with remote sense connected. protected against short circuit and reverse connection. 400 mv 1. ripple and noise are measured with 0.1 uf of ceramic capacitance and 47 uf of electrolytic capacitance on each of the power supply outputs. the output noise requirements apply over a 0 hz to 20 mhz bandwidth. a short coaxial cable with 50ohm scope termination is used. 2. unless otherwise specifed all readings are taken at 120vac input and 25c ambient temperature. 3. 0.4v lead drop is compensated in remote sense. description the mvad065 series switching power supplies utilize advanced component and circuit technologies to deliver high effciency. designed for medical, telecom, and industrial applications to satisfy 1u height design considerations, the mvad065 series measures only 2.0 x 4.0 x 1.3. all models offer universal ac input and compliance to worldwide safety and emc standards. cb test certifcate and test report r eg. -n r . c457 available now at http://power.murata.com/acdc3d mvad065 series 65w 2" x 4" ac-dc power supply converter for full details go to www.murata-ps.com/rohs for full details go to www.murata-ps.com/rohs www.murata-ps.com
mvad065.b01 page 2 of 7 power.murata.com environmental characteristics parameter conditions min. typ. max. units storage temperature range -40 85 c operating temperature range see thermal derating curves -10 70 start up -20 operating humidity non-condensing 10 95 % operating altitude for class i ite equipment deployment -200 5000 m other -200 2000 mtbf telcordia sr-332 m1c3 25c 1m hours shock operating, iec60068-2-27, half-sine 5g, 6ms, 3 times per face, 6 faces complies non-operating, iec60068-2-27, half-sine, 30g, 18ms, 3 times per face, 6 faces complies vibration operating, iec60068-2-6, 1.0g, 10-150hz, 10 minutes per axis, on all 3 axes complies non-operating, iec60068-2-6, 2.0g, 10-150hz, 10 minutes per axis, on all 3 axes complies safety iec60950-1:2005 (2nd edition); am1:2009 ul60950-1 2nd edition,2011-12-19, csa c22.2 no. 60950-1-07, 2nd edition,2011-12 en60950-1:2006 + a11:2009 + a1:2010 + a12:2011 iec60601-1:2005 + corr.1(2006) + corr.2(2007) ansi/aami es60601-1 (2005+c1:09 + a2:10), csa-c22.2 no. 60601-1(2008), mopp ce marking per lvd warranty 2 years outside dimensions 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm) weight mvad065-05 / MVAD065-18 0.285lbs (130g) typical other 0.27lbs (123g) typical protection characteristics parameter conditions min. typ. max. units overvoltage protection mvad065-05 latching (50% load) 110 190 %v1 other latching (60% load) 110 160 overcurrent protection hiccup mode 110 160 %a isolation characteristics parameter conditions min. typ. max. units isolation primary to earth ground (1xmopp) 1500 vac primary to secondary (2xmopp) 4 4000 secondary to earth ground 500 vdc leakage current (under normal conditions) 240vac, 60hz, 25c 300 a 264vac, 60hz, 25c 350 touch current 264vac, 60hz, 25c 100 emissions and immunity characteristic standard compliance input current harmonics iec/en 61000-3-2 class a voltage fluctuation and flicker iec/en 61000-3-3 complies conducted emissions en 55022 class b, class a (at class ii equipment) fcc part 15 class b, class a (at class ii equipment) esd immunity iec/en 61000-4-2 level 4, criterion a radiated field immunity iec/en 61000-4-3 level 2, criterion a electrical fast transient immunity iec/en 61000-4-4 level 3, criterion a surge immunity iec/en 61000-4-5 level 4, criterion a rf conducted immunity iec/en 61000-4-6 level 2, criterion a magnetic field immunity iec/en 61000-4-8 level 2, criterion a voltage dips, interruptions iec/en 61000-4-11 level 3, criterion b 4. at class i equipment. mvad065 series 65w 2" x 4" ac-dc power supply converter
emi considerations for optimum emi performance, the power supply should be mounted to a metal plate grounded to all 4 mounting holes of the power supply. to comply with safety standards, this plate must be properly grounded to protective earth (see mechanical dimension notes). pre-compliance testing has shown the stand- alone power supply to comply with en55022 class a radiated emissions. radiated emission results vary with system enclosure and cable routing paths. performance data mvad065.b01 page 3 of 7 power.murata.com o u t p u t cu r r e n t (a ) m v a d0 6 5 - 05 e ? c i e n c y ( %) 7 3 7 5 7 7 7 9 8 1 8 3 8 5 8 7 8 9 9 1 9 3 0 . 0 0 2 . 0 0 4 . 0 0 6 . 0 0 8 . 0 0 1 0 . 0 0 1 2 . 0 0 9 0 vac 1 1 5 v a c 2 3 0 v a c 2 6 4 v a c 75 77 79 81 83 85 87 89 91 93 95 0 . 0 0 1 . 0 0 2 . 0 0 3 . 0 0 4 . 0 0 5 . 0 0 o u t p u t cu r r e n t (a ) m v a d0 6 5 - 1 2 e ? c i e n c y ( %) 90vac 115vac 230vac 264vac o u t p u t cu r r e n t (a ) m v a d0 6 5 - 18 e ? c i e n c y ( %) 7 5 7 7 7 9 8 1 8 3 8 5 8 7 8 9 9 1 9 3 9 5 0 . 0 0 0 . 5 0 1 . 0 0 1 . 5 0 2 . 0 0 2 . 5 0 3 . 0 0 3 . 5 0 4 . 0 0 9 0 vac 1 1 5 v a c 2 3 0 v a c 2 6 4 v a c 75 77 79 81 83 85 87 89 91 93 95 0 . 0 0 0 . 2 0 0 . 4 0 0 . 6 0 0 . 8 0 1 . 0 0 1 . 2 0 1 . 4 0 o u t p u t cu r r e n t (a ) m v a d0 6 5 - 4 8 e ? c i e n c y ( %) 90vac 115vac 230vac 264vac 75 77 79 81 83 85 87 89 91 93 95 0 . 0 0 0 . 5 0 1 . 0 0 1 . 5 0 2 . 0 0 2 . 5 0 3 . 0 0 o u t p u t cu r r e n t (a ) m v a d0 6 5 - 2 4 e ? c i e n c y ( %) 90vac 115vac 230vac 264vac safety considerations 1. this power supply is a component level power supply intended for use in class i or class ii applications. secondary ground traces need to be suit - ably isolated from primary ground traces when used in class ii applications. 2. when the power supply is used in class ii equipment, all ground traces and components connected to the primary side are considered primary for spacing and insulation considerations. 3. double pole/neutral fusing. mvad065 series 65w 2" x 4" ac-dc power supply converter
performance data mvad065.b01 page 4 of 7 power.murata.com inrush waveform (ac264v 25c) 0 1 0 2 0 3 0 4 0 5 0 6 0 1 0 - 1 0 3 0 5 0 o u tput p o wer ( w ) 7 0 amb i en t temp. ( ) mvad065 -05 thermal deratng 0 2 0 4 0 6 0 8 0 1 0 0 1 0 - 1 0 3 0 5 0 o u tput p o wer (% ) thermal deratng (other) 7 0 amb i en t temp. ( ) mvad065 series 65w 2" x 4" ac-dc power supply converter
mvad065.b01 page 5 of 7 power.murata.com mechanical dimensions C mvad065-05 only dimensions: 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm) all dimens ions in i n c hes ( m m). t o leranc e i s + / - 0 . 02? (0. 5 ) mount ing holes h1 and h2 s hould be eart h -grounded f o r emi purpos e mount ing holes h 2 i s e a r t h ground c onnec t i o n t h i s p o wer s upply requ ires mount ing on s t and o ffs minimum 0 . 2' (5. 0 ) in height o u t put volt age adjust p o t f o r f a c t o ry use 1 pre f e rred scr e w type 0 . 156 0 . 05 4 places maximum s crew head d i ame t e r maximum eart h ground cont act area pcb t op and bottom diame t er 0 . 236" (6.0) m3 ( met r i c scr e w t h r eads) no. 4 -40unc (uni t ed t h read s t andard) input/output connector and signal specification and mating connectors pin description mating housing crimp terminal/pins input connector cn1 : molex 26-62-4030 molex 09-50-8031 with locking ramp molex 6838 series 1 ac line (v-) 3 ac neutral (v+) spade connector: #250 gnd earth ground output connector cn2 : molex 26-60-4060 molex 09-50-8061 with locking ramp molex 6838 series 1, 2 v1 3, 4 dc return 5 -remote sense (nc) 6 +remote sense mvad065 series 65w 2" x 4" ac-dc power supply converter
mvad065.b01 page 6 of 7 power.murata.com mechanical dimensions C mvad065-12x only dimensions: 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm) all dimensions in inches (mm). tolerance is +/-0.02? (0.5) mounting holes h1 and h2 should be earth-grounded for emi purpose mounting holes h2 is earth ground connection this power supply requires mounting on standoffs minimum 0.2 ' (5.0) in height input/output connector and signal specification and mating connectors pin description mating housing crimp terminal/pins input connector cn1 : molex 26-62-4030 molex 09-50-8031 with locking ramp molex 6838 series 1 ac line (v-) 3 ac neutral (v+) spade connector: #250 gnd earth ground output connector cn2 : molex 26-60-4060 molex 09-50-8061 with locking ramp molex 6838 series 1, 2 v1 3, 4 dc return 5 -remote sense (nc) 6 +remote sense mvad065 series 65w 2" x 4" ac-dc power supply converter
mvad065.b01 page 7 of 7 power.murata.com this product is subject to operating requirements and the life and safety critical application policy. click here to view policy. please contact us regarding restricted materials compliance beyond the rohs directive. murata makes no representation that the use of its products in the circuits described herein, or the use of other technical information contained herein, will not infringe upon existing or future patent rights. the descriptions contained herein do not imply the granting of licenses to make, use, or sell equipment constructed in accordance therewith. buyer represents and agrees that it has all the necessary expertise to create and implement safeguards that anticipate dangerous consequences of failures, monitor failures and their consequences, lessen the likelihood of failures that might cause harm, and take appropriate remedial actions. buyer will fully indemnify murata, its affliated companies, and its representatives against any damages arising out of the use of any murata products in safety-critical applications. specifcations are subject to change without notice. ? 2015 murata manufacturing co., ltd. all rights reserved. mechanical dimensions C mvad065-xx 24v and 48v models dimensions: 2.0" x 4.0" x 1.3" (50.8mm x 101.6mm x 33.02mm) all dimensions in inches (mm). tolerance is +/-0.02? (0.5) mounting holes h1 and h2 should be earth-grounded for emi purpose mounting holes h2 is earth ground connection this power supply requires mounting on standoffs minimum 0.2 ' (5.0) in height input/output connector and signal specification and mating connectors pin description mating housing crimp terminal/pins input connector cn1 : molex 26-62-4030 molex 09-50-8031 with locking ramp molex 6838 series 1 ac line (v-) 3 ac neutral (v+) spade connector: #250 gnd earth ground output connector cn2 : molex 26-60-4060 molex 09-50-8061 with locking ramp molex 6838 series 1, 2 v1 3, 4 dc return 5 -remote sense (nc) 6 +remote sense mvad065 series 65w 2" x 4" ac-dc power supply converter murata manufacturing co., ltd. power device product division nagaokakyo-shi, kyoto 617-8555 japan iso 9001 and 14001 registered


▲Up To Search▲   

 
Price & Availability of MVAD065-18

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X